Compactor Solutions Logo

Electricians please use the below chart as a guide for what type of electrical service is needed for a waste compactor.

MOTOR HPVOLTSLOAD AMPSFUSE MAX SIZECIRCUIT BREAKERSERVICE DISCONNECT AMPS
3 HP3/208
3/230
3/460
10.6
9.6
4.8
15
15
10
20
20
15
30
30
30
5 HP3/208
3/230
3/460
16.7
15.2
7.6
30
25
15
40
40
20
30
30
30
10 HP3/208
3/230
3/460
30.8
28
14
50
50
25
80
70
35
60
60
30
15 HP3/208
3/230
3/460
46.2
42
21
60
60
30
90
90
40
60
60
30
20 HP3/208
3/230
3/460
59.4
54
27
100
90
45
125
125
60
100
100
60
30 HP3/208
3/230
3/460
88
80
40
150
150
70
225
200
100
200
200
100
50 HP3/208
3/230
3/460
143
130
65
250
225
100
350
350
150
400
400
100
3/4 HP1/120
1/230
13.8
6.9
20
10
20
15
30
30
3 HP1/280
1/230
18.7
17
30
25
45
40
30
30
5 HP1/208
1/230
30.8
28
50
45
80
70
60
60
10 HP1/208
1/230
55
50
100
90
125
125
100
100